Protected Distribution System (PDS) Construction - Point of Presence (PoP) and Terminal Equipment Protection. This requirement concerns security of both the starting and ending points for PDS within proper physically protected and access controlled environments.
An XCCDF Rule
Description
<VulnDiscussion>A PDS that is not constructed and physically protected as required could result in the covert or undetected interception of classified information. REFERENCES: CJCSI 6510.01F, INFORMATION ASSURANCE (IA) AND SUPPORT TO COMPUTER NETWORK DEFENSE (CND), Enclosure C, paragraph 35.c. DOD 5220.22-M (NISPOM), Incorporating Change 2, 18 May 2016 Chapter 5, Section 4, paragraphs 5-402.c. and 5-403 DOD Manual 5200.01, Volume 3, 24 February 2012, SUBJECT: DOD Information Security Program: Protection of Classified Information, Encl 4, para 3.b. and 4.a. NIST Special Publication 800-53 (SP 800-53), Rev 4, Controls: PE-4, SC-7, and SC-8 CNSSI No. 7003, September 2015, Protected Distribution Systems (PDS), Section IV, paragraph 7., Section VIII, paragraphs 22, 25, 26 & paragraph 27.b. & c. and Section X, paragraph 30.a.</VulnDiscussion><FalsePositives></FalsePositives><FalseNegatives></FalseNegatives><Documentable>false</Documentable><Mitigations></Mitigations><SeverityOverrideGuidance></SeverityOverrideGuidance><PotentialImpacts></PotentialImpacts><ThirdPartyTools></ThirdPartyTools><MitigationControl></MitigationControl><Responsibility></Responsibility><IAControls></IAControls>
- ID
- SV-245728r917319_rule
- Severity
- High
- Updated
Remediation - Manual Procedure
This fix concerns security requirements for the physical locations of both the starting and ending points for Protected Distribution Systems (PDS) within a physical enclave.
All of the following requirements must be met:
1. The PDS must originate within the room or area containing the SIPRNet Point of Presence (PoP) for the facility or area, which must be in a Secret or above Secure Room, Vault, SCIF or alternatively in an Information Processing Systems (IPS) Container with SIPRNet connected equipment (router/switch/PC/laptop/multi-function device (e.g., printer, copier, fax)). An IPS container is a specially designed safe for secured operation of classified network and end user equipment.